Projects

LV Switchgear

LV Switchgear

LV Switchgear

Kettering General Hospital

Knight Electrical Switchgear were asked to manufacture, deliver and assemble in position a switchboard for connecting 4No. 500kVA Generators to several outgoing main loads.

The switchboard was assembled, tested and witness tested at our premises before being split into 6 shipping sections for delivery to site, where our site engineers moved it into it’s final position, re-connected and re-retested.

Switchboard Specification

  • Description: Free standing, floor mounted, back to back
  • Access: Front and rear
  • IP Rating: 42
  • Colour: RAL 7035 (light grey)
  • Segregation and separation: Form 4, type 6
  • Cable entry and exit: Above and below
  • Dimensions: 2100 mm(h) x 4000mm(w) x 1350mm(d)
  • Busbars: 4000A
  • Fault rating: 50kA/1Sec
  • Devices: ACB’s & MCCB’s